Product introduction
KYN28-12 armored removable AC metal-enclosed switchgear (hereinafter referred to as switch cabinet) is a new product designed and developed by our company on the basis of absorbing advanced manufacturing technology at home and abroad. It can replace various old-type metal-enclosed switchgear, such as KYN1-12, JYN2-12, etc. series of products.
Product Advantages
The enclosure is assembled entirely using bolts, ensuring high mechanical strength while maintaining a neat and aesthetically pleasing appearance.
The cabinet doors are powder-coated, providing excellent impact resistance and corrosion resistance.
The enclosure offers an IP4X degree of protection. (The material can be changed to steel plate upon customer request.)
The switchgear can be equipped with ABB's VD4-type vacuum circuit breakers or C3-series fixed load-break switches; it is also compatible with various domestically manufactured vacuum circuit breakers.
Regardless of the circuit breaker selected, the air-insulated clearance for bare conductors is at least 125 mm, while the composite insulation clearance exceeds 60 mm.
The circuit breakers feature the distinct advantages of a long service life, minimal maintenance requirements, and a compact footprint.
Normal Operating Conditions
| Ambient air temperature | Upper limit +40°C, lower limit -10°C |
| Relative humidity | Daily average ≤95%, monthly average ≤90% |
| Altitude | ≤1000 meters (for altitudes >1000 meters, temperature rise limits must be adjusted) |
| Seismic intensity | Not exceeding 8 degrees |
PS:Environments free from fire or explosion hazards, severe pollution, chemical corrosion, and intense vibration. Should operating conditions fall outside these parameters, the permissible limits and necessary technical measures shall be determined through consultation between the user and our company.
Products Description
|
Project |
Unit |
Parameter |
|
| Rated voltage |
KV |
3,6,7.2,12 |
|
| Rated frequency |
Hz |
50 |
|
| Rated current of circuit breaker |
A |
630,1250,1600,2000,2500,3150 |
|
| Rated current of switchgear |
A |
630,1250,1600,2000,2500,3150 |
|
| Rated short-time withstand current (4s) |
KA |
16,20,25,31.5,40,50 |
|
| Rated peak withstand current (peak value) |
KA |
40,50,63,80,100,125 |
|
| Rated short-circuit breaking current |
KA |
16,20,25,31.5,40,50 |
|
| Rated short-circuit making current (peak value) |
KA |
40,50,63,80,100,125 |
|
|
Rated insulation level |
1-min power-frequency withstand voltage |
KV |
24,32,42 |
| Lightning impulse withstand voltage |
KV |
40,60,75 |
|
| Degree of protection | IP4X for the enclosure; IP2X when the doors to the isolation compartment or circuit-breaker compartment are open. | ||
Equipment List
| Symbol |
Name |
Symbol | Name |
|
HK1 |
Auxiliary switch (test position) |
HK1 |
Auxiliary switch (operating position) |
|
HQ |
Closing electromagnet |
HQ |
Microswitch (motor cut-off) |
|
TQ |
Opening electromagnet |
TQ |
Microswitch (motor cut-off) |
|
HK |
Auxiliary switch (main contacts) |
HK |
Microswitch (anti-pumping contactor cut-off) |
|
D |
Energy-storage switch |
D |
Microswitch (spring-charging signal) |
|
CZ |
Terminal block |
CZ |
Microswitch (manual local tripping) |
|
ZLC |
Anti-pumping contactor |
ZLC |
Microswitch (manual local tripping) |
Main Circuit Schematic
| Scheme Number |
01 |
02 |
03 |
04 |
05 |
06 |
|
| Cabinet Dimensions (Width × Depth × Height) mm |
800/1000×1500×2300 |
800/1000×1500×2300 |
800/1000×1500×2300 |
800/1000×1500×2300 |
800/1000×1500×2300 |
800/1000×1500×2300 |
|
| Rated Current (A) |
630~3150 |
||||||
| Main Electrical Components | Vacuum Circuit Breaker (ZN63A or VD4) |
1 |
1 |
1 |
1 |
1 |
1 |
| Current Transformer (LZZBJ9 Series) |
2 |
2 |
2 |
3 |
3 |
3 |
|
| Earthing Switch (JN15) |
1 |
1 |
1 |
1 |
|||
| Lightning Arrester (HY5W) |
3 |
3 |
|||||
| Power Inbound/Outbound | Power Inbound/Outbound | Power Inbound/Outbound | Power Inbound/Outbound | Power Inbound/Outbound | Power Inbound/Outbound | ||
| Notes |
1. For a rated current of 1600A or above, the cabinet width is 1000mm. 2. For switchgear used at high altitudes (3000m–4000m), the rated current is 1250A. |
Cabinet width is 1000mm. | |||||